1. SAFETY
1.4 EARTHING AND EARTH FAULT PROTECTION
The AC drive must always be earthed with an earth conductor that is connected to the earth terminal that is identified with the
symbol . Not using an earth conductor can cause damage to the drive.
The touch current of the drive is more than 3.5 mA AC. The standard EN 61800-5-1 tells that 1 or more of these conditions for
the protective circuit must be true.
The connection must be fixed.
a) The protective earth conductor must have a cross-sectional area of minimum 10
㎟
Cu or 16
㎟
Al. OR
b) There must be an automatic disconnection of the mains, if the protective earth conductor breaks. See chapter 4 Power
cabling. OR
c) There must be a terminal for a second protective earth conductor in the same crosssectional area as the first protective
earth conductor.
Table 2: Protective earthing conductor cross-section
The values of the table are valid only if the protective earthing conductor is made of the same metal as the phase conductors.
3
CAUTION!
Make sure that the EMC level of the AC drive is correct for your mains. See chapter 6.5 Installation in an IT system.
An incorrect EMC level can cause damage to the drive.
CAUTION!
Prevent radio interference. The AC drive can cause radio interference in a domestic environment.
NOTE!
If you activate the autoreset function, the motor starts automatically after an automatic fault reset. See the Ap-
plication Manual.
NOTE!
If you use the AC drive as a part of a machine, the machine manufacturer must supply a mains disconnection de-
vice (refer to EN 60204-1).
CAUTION!
Cross-sectional area of the phase conductors (S)
[
㎟
]
The minimum cross-sectional area of the protective
earthing conductor in question [
㎟
]
S
≤
16
S
16
≺
S
≤
35
16
35
≺
S
S/2
N800A
Summary of Contents for N800 Series
Page 2: ...ISSUEDATE 2015 06 26 VER 1 ...
Page 3: ......
Page 19: ...3 MOUNTING 3 2 2 WALL MOUNTING OF MR5 Fig 3 ThedimensionsoftheACdrive MR5 13 N800A ...
Page 20: ...3 MOUNTING 3 2 3 WALL MOUNTING OF MR6 Fig 4 ThedimensionsoftheACdrive MR6 14 N800A ...
Page 21: ...3 MOUNTING 3 2 4 WALL MOUNTING OF MR7 Fig 5 ThedimensionsoftheACdrive MR7 15 N800A ...
Page 23: ...3 MOUNTING 3 2 6 WALL MOUNTING OF MR8 IP00 Fig 7 ThedimensionsoftheACdrive MR8 IP00 17 N800A ...
Page 52: ...4 POWERCABLING 46 3 Removethecablecover MR8 MR9 N800A ...
Page 53: ...4 POWERCABLING 47 4 Removethecableentryplate MR8 MR9 N800A ...
Page 54: ...4 POWERCABLING 48 5 MR9only Loosenthescrewsandremovethesealingplate N800A ...
Page 55: ...4 POWERCABLING 49 6 RemovetheEMCshieldplate A ThewingnutinMR8 A MR9 N800A ...
Page 80: ...5 CONTROLUNIT 74 Fig 30 Thegalvanicisolationbarriers A Thecontrolunit B Thepowerunit N800A ...
Page 101: ......