1. Technical Specifications
Product type High bay microwave DALI sensor (Daylight harvest)
Operating voltage 120~277VAC 50/60Hz
Switched power Maximum 20pcs DALI devices Maximum 40mA
Power consumption < 0.5W
Detection angle 360
o
Detection area (DxH) 10 x 15m (Maximum)
Mounting height 15m (Maximum)
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 50 ~ 500Lux , Disable
Warmming-up time 20s
Operating temperature -20
o
C ~ +50
o
C
IP rating IP65
3. Rotary Switch Settings
Detection
range
Channel
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
5s
1min
5min
5min
5min
5min
10min
10min
10min
10min
20min
20min
30min
30min
30min
5s
10s
5min
10min
+∞
+∞
+∞
30min
+∞
+∞
+∞
1h
+∞
+∞
+∞
+∞
10s
10%
10%
10%
10%
10%
30%
10%
10%
10%
30%
10%
30%
10%
30%
50%
10%
Disable
50Lux
50Lux
75Lux
100Lux
200Lux
50Lux
75Lux
100Lux
200Lux
100Lux
200Lux
100Lux
200Lux
400Lux
100Lux
Hold
time
Stand-by
time
Stand-by
dimming level
Daylight
threshold
A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
Note: settings can also be changed by remote control HRC-11. The last action controls.
8
HIGH BAY MICROWAVE DALI SENSOR HMW34
Installation and Instruction Manual
Rotary switch preset (Please
see the location in 2. Installation)
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically
whenever artificial light is not required (natural light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at "+∞", the fixture never switches off even when natural light
is sufficient.
4.2 Lux Off Function
4. Functions
Daylight sensor measures the available natural light of the surrounding, calculates how much electrical
light is needed to reach the total lux expected. The demand is given to the LED driver by DALI signal, so as
to deliver the needed amount of electric light.
4.1 Daylight Harvest (Daylight Regulating)
0
24
Light level
Time (hrs)
Normal Electric Light
Daylight controlled light
Energy Saving Zone
Natural light
Hold time
Stand-by time
HMW34-20181126-A1
2. Installation
Warnings:
1. Installation of the sensor involves connecting it to the mains supply. This work must be
carried out by a specialist in accordance with electrotechnical regulations.
2. Disconnect power supply before installing.
The light will flash ONCE rapidly after receiving the command from the remote controller.
Note: There is no load indication (the light will not flash) when button ON/OFF, POWER 100%
or POWER 80% is pressed.
4.3 Load Indication
A. Ceiling mount
B. Screw to the Luminaire by conduit
C. Attach to the shade by clamp
91.5
59.3
57.3
47.5
4.1
80.7
75
4.1
66.6
81.5
59.6
66.6
89.9
0.825”
75
64
59.3
57.3
35.2
47.5
84.5
59.3
ぶ
29
163.2
66.6
75
33.7
15
28.5
4.5
ぶ
4.5
59.6
Sensor module
Photocell
LED indicator
Infrared receiver
Rotary switch
Cable entry
Installation rack
Photocell
Sensor module
LED indicator
Infrared receiver
Rotary switch
Cable entry
Sensor module
Photocell
LED indicator
Infrared receiver
Rotary switch
Angle adjustment
Luminaire clamp