1. Technical Specifications
Product type High bay microwave motion sensor (Daylight harvest)
Operating voltage 120~277VAC 50/60Hz
Rated load Resistive:700W@120V; 1600W@220-277V;
Capacitive:400VA@120V; 800VA@220-277V;
Power consumption < 1W
Detection angle 360
o
Detection area (DxH) 12 x 12m (Maximum)
Mounting height 15M(Maximum)
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 50 ~ 500Lux, Disable
Warmming up time 20s
Operating temperature -20
o
C ~ +50
o
C
IP rating IP42
3. Rotary Switch Settings
A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
Note: settings can also be changed by remote control HRC-11. The last action controls.
8
SURFACE MOUNT HIGH BAY MOTION SENSOR HMW12
Installation and Instruction Manual
Rotary switch preset (Please
see the location in 2. Installation)
4. Functions
The motion sensor is employed, but only activated on the manual press of the push switch,
The light remains on during presence and dims down in absence, eventually switching off
automatically after the stand-by time has expired.
Note: in this mode, the push terminal used for the ‘manual on’ switch input.
End-user can choose either function 4.3 or 4.4 for application. Default function is 4.3.
4.2 Lux Off Function
4.4 Semi-auto Function (Absence Detection)
4.3 Manual Override
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off
the lights manually, or adjust the light brightness during motion hold-time. This makes the
product more user-friendly and offers more options to fit for extra-ordinary demands.
* Short push (<1s): on/off function;
ON
→
OFF: the light turns off immediately and cannot be lighten for a certain time (equals to
hold time preset) even there is movement is detected. After this period, the sensor goes back
to auto sensor mode.
OFF
→
ON: the light turns on 100% and goes to auto sensor mode, even when ambient
Lux level exceeds the daylight threshold.
* Long push (>1s): adjust the target lux level by turning the light up or down. Both the
adjustment on remote control and push switch can overwrite each other,
the last adjustment remains in memory.
HMW12-20170309-A1
2. Installation
Warnings:
1. Installation must be carried out by a
qualified engineer in accordance with
local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may
cause mis-triggering.
4. Ensure environmental conditions are
suitable for electronic equipment
29
50.2
Direct junction “J” box mounting
a. Separate control board (A) from facia (B)
& Surface box (C). C is not required.
b. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box.
d. Set-up sensor modes as per sections 3 & 4
of this manual.
e. Clip facial plate (B) to control board (A).
Surface mount assembly
a. Separate control board (A) from facia (B) &
Surface box (C).
b. Securely mount surface box (C) to a flat and
solid surface.
c. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of
this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).
32.5
53.7
C - Surface box
B - Facia Cover
A - Control Board
Rotary switch preset
Photocell
Infrared receiver
HF Sensor module
LED indicator
4.1 Daylight Harvest (Daylight Regulating)
Daylight sensor measures the available surrounding natural light, calculates how much electrical light is
needed to reach the total lux expected. The demand is given to the LED driver by 1-10V signal, so as to
deliver the needed amount of electric light.
0
24
Light level
Time (hrs)
Normal Electric Light
Daylight controlled light
Energy Saving Zone
Natural light
Hold time
Stand-by time
Detection
range
Channel
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
5s
1min
5min
5min
5min
5min
10min
10min
10min
10min
20min
20min
30min
30min
30min
5s
10s
5min
10min
+∞
+∞
+∞
30min
+∞
+∞
+∞
1h
+∞
+∞
+∞
+∞
10s
10%
10%
10%
10%
10%
30%
10%
10%
10%
30%
10%
30%
10%
30%
50%
10%
Disable
50Lux
50Lux
75Lux
100Lux
200Lux
50Lux
75Lux
100Lux
200Lux
100Lux
200Lux
100Lux
200Lux
400Lux
100Lux
Hold
time
Stand-by
time
Stand-by
dimming level
Daylight
threshold
The light dims to minimum level even switches off completelly if ambient daylight is
sufficient (natural light level exceeds target lux level), no matter it is during hold-time or
stand-by time, with or without motion.
Note: if the stand-by time is preset at "+∞", the light never turns off even when natural light
is sufficient.