background image

Mechanical Structure

75.2

78

70.5

62

1.  Ceiling (drill hole 65mm)
2.  Carefully prise off the cable clamps.
3.  Make connections to the pluggable
     terminal blocks.
4.  Insert plug connectors and secure using
     the provided cable clamps, then clip
     terminal covers to the base.
5.  Fit detection blind (if required) and 
     desired lens.
6.  Clip fascia to body.
7.  Bend back springs and insert into ceiling.

4

5

2

3

1

65mm

* Install lens as required

7

2

1

* Install blind as required

A

B

6

3

2

1

Wire Preparation

0.75 - 2.5mm

8mm

(min 6mm, max 11mm)

Pluggable screw terminal.  It is recommended to make
connections to the terminal before fitting to the sensor.

Subject to change without notice.

Edition: 30 Jun. 2021      Ver. A0      Page 2/9

Note:We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors 
from false-triggering.

Summary of Contents for HIR27

Page 1: ...eded natural light has proirity synchronization control TX T X T X RX Synchronisation terminal for grouping of sensors Input Characteristics Stand by power Model No HIR27 Operating voltage 0 5W Appr 20s Warming up 220 240VAC 50 60Hz Switched power Max 40pcs devices 80mA EMC standard EMC Safety standard LVD Certification EN55015 EN61000 EN61547 CB CE EMC LVD RCM ROHS compliance Safety and EMC EN606...

Page 2: ...lens 6 Clip fascia to body 7 Bend back springs and insert into ceiling 4 5 2 3 1 65mm Install lens as required 7 2 1 Install blind as required A B 6 3 2 1 Wire Preparation 0 75 2 5mm 8mm min 6mm max 11mm Pluggable screw terminal It is recommended to make connections to the terminal before fitting to the sensor Subject to change without notice Edition 30 Jun 2021 Ver A0 Page 2 9 Note We recommend t...

Page 3: ...rn for single person Ta 20 O C Recommended ceiling mount installation height 2 5m 6m max 64m2 Ø 9m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m max 50m2 Ø 8m max 38m2 Ø 7m max 38m2 Ø 7m max 38m2 Ø 7m Blind Option 1 Aisle Detection Optional Accessory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Blind Option 2 1...

Page 4: ...0m2 Ø 5m max 20m2 Ø 5m max 20m2 Ø 5m 2 HIR27 R Reinforced Low bay A Tangential movement Tangential max 10m h max 6m A B Radial movement Radial max 5m h max 6m B Optional Accessory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Valid Range Blind Option 1 Aisle Detection Blind Option 2 180 O Detection Valid Range insensitive sensitive ins...

Page 5: ...essory Ceiling Surface Mount Box HA03 Optional Accessory Blind Insert for Blocking Certain Detection Angles 75 Ø 94 Valid Range Blind Option 1 Aisle Detection Blind Option 2 180 O Detection Valid Range Radial B Tangential A 2 5m Mount height 11m 12m 10m 8m 6m max 104m2 Ø 11 5m max 50m2 Ø 8m max 154m2 Ø 14m max 227m2 Ø 17m max 269m2 Ø 18 5m max 314m2 Ø 20m max 7m2 Ø 3m max 7m2 Ø 3m max 7m2 Ø 3m max...

Page 6: ...eiling Surface Mount Box HA03 75 Ø 94 4 HIR27 RH Reinforced High bay with 3 Pyro Tangential max 30m h max 12m A Radial max 4m h max 12m B Radial B Tangential A 2 5m Mount height 11m 12m 10m 8m 6m max 154m2 Ø 14m max 38m2 Ø 7m max 314m2 Ø 20m max 531m2 Ø 26m max 615m2 Ø 28m max 707m2 Ø 30m max 7m2 Ø 3m max 7m2 Ø 3m max 7m2 Ø 3m max 13m2 Ø 4m max 13m2 Ø 4m max 13m2 Ø 4m A Tangential movement B Radia...

Page 7: ... is manual override 2 3 Semi auto Mode Absence Detection Manual Override 2 Short Push 1s on off function On Off the light turns off immediately and cannot be triggered ON by motion until the expiration of pre set hold time After this period the sensor goes back to normal sensor mode Off On the light turns on and goes to sensor mode no matter if ambient Lux level exceeds the daylight threshold or n...

Page 8: ...d Scene program 1 key commissioning Detection range All buttons in this zone are disabled 1 Press button Start to program 2 Select the buttons in Detection range Daylight threshold Hold time Stand by time Stand by dimming level to set all parameters 3 Press button Memory to save all the settings programmed in the remote control 4 Press button Apply to set the settings to each sensor unit s For exa...

Page 9: ...dimming level to set the stand by dimming level at 10 20 30 50 All buttons are disabled Auto configuration function 1 Press button Shift the red LED starts to flash 2 Select a time period and the sensor will do light level measurement and determine save the lowest light level commission line with 100 light on so as to set the target lux level automatically Note 1 Make sure the light level measurem...