background image

2. Installation 

1. Technical Specifications

Product type                                  Tri-level control PIR DALI sensor

Operating voltage                           9.5 ~ 22.5VDC ( suitable DALI power supply)

Input current                                  < 8mA

Power consumption                        < 0.5W

Detection angle                              360

o

Detection area (DxH)                      10 x 3m (Tangential)

Mounting height                             5m (Maximum)

Detection range                             10% / 50% / 75% / 100%

Hold time                                       2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min

Stand-by time                                0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞ 

Stand-by dimming level                  10% / 20% / 30% / 50%

Daylight threshold                          2Lux / 10Lux / 50Lux / Disable

Warmming-up time                        30s

Operating temperature                   -20

o

C ~ +50

o

C

3. Rotary Switch Settings

A rotary switch is built inside the sensor for 
scene selection / fast programming. Total 
16 channels available:

Note: settings can also be changed by remote control HRC-11. The last action controls.

FLUSH MOUNT PIR DALI SENSOR HIR23

Installation and Instruction Manual 

Rotary switch preset (Please 
see the location in 2. Installation)

DALI group selection (Please 
see the location in 2. Installation)

Warnings: 

1. Installation of the sensor involves connecting it to the mains supply. This work must be 
    carried out by a specialist in accordance with electrotechnical regulations.
2. Disconnect supply before installing.

Detection 
range 

Channel

0

1

2

3

4

5

6

7

8

9

A

100%

100%

100%

100%

100%

100%

100%

100%

100%

100%

100%

75%

50%

100%

100%

100%

5s

1min

5min

5min

5min

5min

5min

10min

10min

10min

10min

10min

10min

30min

30min

5s

10s

5min

10min

30min

0s

+∞

+∞

10min

30min

+∞

+∞

+∞

+∞

+∞

+∞

10s

10%

10%

10%

10%

Disable

10%

30%

10%

10%

10%

30%

10%

10%

10%

30%

10%

Disable

2Lux

10Lux

30Lux

10Lux

30Lux

Disable

2Lux

10Lux

30Lux

Disable

30Lux

10Lux

50Lux

Disable

2Lux

Hold 
time

Stand-by 
time 

Stand-by 
dimming level 

Daylight 
threshold

5. Functions

Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas require a 
light change notice before switch-off.
It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time: motion 
hold-time and stand-by period; Selectable daylight threshold and freedom of detection area. 

This DALI sensor is designed for incoporated in the DALI system, taking command from the DALI master, 
accepting and carrying out the grouping work with up to 64 lumanaires. It can switch on/off, or dim the 
assigned group members and feed back the status to the DALI master.

By connecting the DALI terminals in parallel (see wiring diagram), no matter which sensor detects motion, 
all HMW23 in the group will turn on the lights when surrounding natural light is below the daylight 
threshold. The sensor antenna is shared and the detection area could be widely enlarged in this way. 

5.1 Tri-level Control (Corridor Function)

5.2 Synchronization Function

4. DALI group selection

DALI group configuration can be done on PC or on the rotary switch:

1. There are 16 channels available on the rotary switch. “0” is 
    for DALI broadcast, the rest 15 channels is for end user to 
    define the application unit.
2. PC grouping can overwrite rotary switch grouping, the last 
    setting controls.
3. The rotary switch channel is corresponding to the groups
    listed below:

Switch channel

DALI group

Switch channel

DALI group

0

1

2

3

4

5

6

7

broadcast

group 0

group 1

group 2

group 3

group 4

group 5

group 6

8

9

A

B

C

D

E

F

group 7

group 8

group 9

group 10

group 11

group 12

group 13

group 14

Infrared receiver

Photocell

LED indicator

PIR

Rotary switch preset

1

3

4

2

(1) Sensor inset
(2) Lens pluggable
(3) Protection cover (covers the 
     high-voltage terminals, and leaves 
     the DALI terminals exposed).
(4) Ceiling (drill hole O 70mm).

64.7

o85

68.1

73.3

56

Blind

70mm

Note: the blind can be plugged to the cover for 
         reducing detection angle if necessary.

HIR23-20160912-A2