1. Technical Specifications
Product type RF wireless microwave motion sensor (tri-level control)
Operating voltage 220~240VAC 50/60Hz
Power consumption < 1.5W
Detection angle 360
o
Detection area (Max.)*
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 2 ~ 500Lux, Disable
RF transmission distance 30 meters in the open area
RF frequency 868MHz (FSK mode)
Warming up time 20s
Operating temperature -20
o
C ~ +50
o
C
IP rating IP65
8
2. Installation
Warnings:
1. Installation must be carried out by a qualified engineer in accordance with local
regulations.
2. Disconnect power supply before installing.
3. Install to a solid surface - vibrations may cause mis-triggering.
4. Ensure environmental conditions are suitable for electronic equipment
Rotary switch
for RF grouping
HC034RF (RF receiver)
RF antenna
Infrared remote receiver
1-10V+
1-10V-
L’
N N L
71.5
4.2
37.5
38.3
25
11.8
78.2
87
Installation hole
Installation and Instruction Manual
HIGH BAY RF WIRELESS MICROWAVE
MOTION SENSOR HMW38/RF + HC034RF
HF
HMW38/RF-20181220-A1
Product type RF wireless receiver
Operating voltage 220-240V 50Hz
Rated load Capacitive:400W; Resistive:1200W
IP rating IP20
3. Rotary Switch for RF grouping
4. Functions
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas
it requires a light change notice before switch-off.
It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time:
motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection
area.
4.1 Tri-level Control (Corridor Function)
15 channels are available for fast grouping via rotary switch on both HMW38/RF and HC034RF.
By simply selecting the same channel on each unit, the grouping is automatically completed.
Noted:channel "0" is not for fast grouping, and sensors can only be grouped by remote control.
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically
whenever artificial light is not required (natural light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at "+∞", the fixture never switches off even when natural light
is sufficient.
4.2 Lux Off Function
The light will flash ONCE rapidly after receiving the command from the remote controller.
Note: There is no load indication (the light will not flash) when button ON/OFF, POWER
100% or POWER 80% is pressed.
4.3 Load Indication
commander
receiver
HMW38/RF
HC034RF
Rated load
A. Ceiling mount
B. Screw to the Luminaire by conduit
C. Attach to the shade by clamp
91.5
59.3
57.3
47.5
4.1
80.7
75
4.1
66.6
81.5
59.6
66.6
89.9
0.825”
75
64
59.3
57.3
35.2
47.5
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Angle adjustment
Luminaire clamp
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Cable entry
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Cable entry
Installation rack
84.5
59.3
ぶ
29
163.2
66.6
75
33.7
15
28.5
4.5
ぶ
4.5
59.6
Installation Height : 20m (forklift) 15m (person)
Detection Range (Ø) :20m
24.5
1000W (resistive);
800VA (capacitive)