Hytronik HC019V/DH Quick Start Manual Download Page 1

Subject to change without notice.

Edition: 26 Feb. 2020      Ver. A0      Page 1/7

One-Key
Commissioning

One-key commissioning via programmable remote control

Applications

Occupancy detector with daylight harvest suitable for building into the fixture:

     Office / Commercial Lighting

     Classroom

Use for new luminaire designs and installations

Features

IP20

RED

Stand-by power

EMC standard (EMC)
Safety standard (LVD)

Certification

Radio Equipment (RED) 

EN55015, EN61000

Semko, CB, CE , EMC, RED, RCM

1200W

EN60669

Model No.

HC019V/DH

220~240VAC  50/60Hz 

Mains voltage

Load ratings:

EN300440, EN301489, 

EN62479

<0.8W

Technical Data

Input Characteristics 

Safety and EMC

800VA

Capacitive

Resistive

Sensor Data

Tc: +80

O

Operation temperature
Case temperature (Max.)

Ta: -20

O

C ~ +60

O

C

Environment 

IP20  

IP rating

Model No.

2 ~ 50 lux, disabled

5s ~ 30min (selectable)

0s ~ 1h, +∞ (selectable)

10% /30%  

50% / 100%

30

O

 ~ 150

O

<0.2mW

5.8GHz +/- 75MHz

High Frequency (microwave) 

Sensor principle 

Operation frequency

Transmission power
Detection range

Daylight threshold
Stand-by period
Stand-by dimming level

Hold-time

Sensitivity

DIP Switch Settings:

Detection angle

Max. (

 

O

 

x H) 12m x 6m

HC019V/DH

Daylight Harvest HF Sensor 

Fixture Built-in Sensor with Photocell Advance

TM

 and Remote Control

20s

Warming-up

Tri-level dimming control based upon occupancy (also known as corridor function)

Special photocell to measure and differentiate natural light from LED light from behind the fixture cover

TM

5-Year Warranty

Zero crossing detection circuit reduces in-rush current and prolongs relay life

1-10V dimming control method

Photocell Advance

Loop-in and loop-out terminal for efficient installation

Loop in

Loop out

Synchronised dimming with multiple sensor circuits

Synchronisation

control

RX

TX

TX

TX

Daylight harvest function to regulate light output for maintaining required lux level

HC019V/DH

Summary of Contents for HC019V/DH

Page 1: ...ctable 0s 1h selectable 10 30 50 100 30 O 150 O 0 2mW 5 8GHz 75MHz High Frequency microwave Sensor principle Operation frequency Transmission power Detection range Daylight threshold Stand by period Stand by dimming level Hold time Sensitivity DIP Switch Settings Detection angle Max O x H 12m x 6m HC019V DH Daylight Harvest HF Sensor Fixture Built in Sensor with Photocell Advance TM and Remote Con...

Page 2: ...tches off completely after the stand by period Note 1 The light automatically turns on at target dim level or turns off based upon ambient natural light lux level during stand by period if it is preset to 2 The target lux level can be adjusted by RC or a long press on the push switch 2 50Lux Hold time 5s 30min Synchronisation control RX TX T X T X 6 6 0 Detection Pattern One Key Commissioning Func...

Page 3: ...erride function for end user to switch on off or adjust the target lux level by push switch which makes the product more user friendly and offers more options to fit some extra ordinary demands Semi auto Mode Absence Detection 5 Note end user can choose either function or function for application Default function is manual override 4 5 The light turns on full and the sensor stays in sensor mode Th...

Page 4: ... driver Maximum 800W HC019V DH HC019V DH HC019V DH LED Driver LED Driver LED Driver 1 10V SYNC 1 10V L N L N L P LED 1 10V L N LED 1 10V L N LED N L Note this 1 10V output is isolated SELV output Do not connect the 1 10V terminals on driver X to Driver Y P N L 1 10V SYNC 1 10V LED LED driver Y 1 10V LED LED driver X Multiple sensors control the same group of ballast driver Detection Pattern Wall m...

Page 5: ...tons to adjust the light output brightness and set a new target lux level The built in daylight sensor can measure ambient daylight level from behind the diffuser and calculates how much artificial light is needed to maintain the target lux level Brightness Scene program 1 key commissioning 1 Press button Start to program 2 Select the buttons in Detection range Daylight threshold Hold time Stand b...

Page 6: ...min 5min 10min 30min 1h Note 0s means on off control means the stand by time is infinite and the light is effectively controlled by the daylight sensor off when natural light is sufficient and automatically on at dimming level when insufficient Press the button in zone stand by dimming level to set the stand by dimming level at 10 20 30 50 All buttons in this zone are disabled 1 Detection Range 2 ...

Page 7: ...nload knowledge Hytronik Standard Guarantee Policy 5 Stand by dimming level 4 Stand by period corridor function I 0s II 10s III 1min IV 5min V 10min VI 30min VII 1h VIII This is the time period you would like to keep at the low light output level before it is completely switched off in the long absence of people I 10 II 30 1h 10min 30min 5min 1min 10s 8 7 6 0s I II III IV V VI VII VIII 30 10 9 I I...

Reviews: