background image

1. Technical Specifications

HC005S/I-20210128-A0

3. Functions

1. Lux Off Function
The built-in daylight sensor can measure ambient natural light and switch off the fixture 
automatically whenever artificial light is not required (natural light lux level exceeds daylight 
threshold).

2. Zero-cross Relay Operation
Designed in the software, the sensor switches on/off the load right at the zero-cross point, to 
ensure the in-rush current is minimised, enabling the maximum life-time of the relay.

3.  Loop-in and Loop-out Terminal
Double L N terminal makes it easy for wire loop-in and loop-out, and saves the cost of 
terminal block and assembly time.

Product Type:

Operating Voltage:
HF System:
Transmission Power:
Rated Load:

Detection Angle:
Power Consumption: 
Detection Range :
Time Setting:
Mounting: 
Light Control:
Working Temperature:

ON/OFF Control Microwave Motion Sensor
Against wireless signals interference 
220-240VAC  50/60Hz
5.8GHz CW radar
< 0.2mW
800W (resistive load)
400VA (capacitive load)
30~150°
< 0.5W
Max. 10 meters in diameter, adjustable
5s ~ 30 min.
Indoors, Ceiling & walling mounted
2~50 lux, disable

-35 ~ +70°C

*

2. Dimensions (mm)

4. Wiring Diagram

Installation and Instruction Manual 

SUPER COMPACT ON/OFF HF SENSOR HC005S/I

To connect several standard control gear with 1 sensor (ON/OFF function), the 
wiring should be.

Daylight threshold

Hold-time

Detection area

Antenna module

Daylight sensor

Intallation hole

L’

L

N

N

65

36.5

4.2

71.7

80.5

26

12.1

23.8

Control gear

Control gear

Control gear

L

L’

N N

N

L

N

L

N

L

N

L

With Tridonic switchDIM ballast / driver ( Excel ballast/driver, corridor function) , 
this sensor can also achieve tri-level dimming control:

Switch-dim.

Switch-dim.

Switch-dim.

Control gear

Control gear

Control gear

L

L’

N N

N

L

N

L

N

L

N

L

  

5. Settings

Detection Range

I - 100%
II - 75%
III - 50%
IV - 30%
V -  Sensor OFF

Sensor 

 

OFF

Hold Time

I - Walk test mode 5s
II - 30s
III - 1 minute
IV - 5 minutes
V - 20 minutes
VI - 30 minutes

Select the dip switch configuration for the full brightness on-time after presense 
detection. Please note that this function is disabled when the natural daylight 
exceeds the daylight threshold setting more than 5 minutes.

This determines the effective range of the motion detector and is set by DIP 
switches at the sensor itself, refer to figure. Note that reducing the sensitivity 
will also narrow the detection range. The following settings are available. 

I - Disable 
II - 50 lux
III - 20 lux
IV - 5 lux
V - 2 lux

* In disable mode the fixture(s) will always be on with motion detection 
regardless of the ambient lux level.

Daylight Sensor

This setting holds off the 100% light output should there sufficient daylight and 
is set using DIP switches at the sensor, refer to figure. The following settings are 
available.

1 2 3

4 5 6

7 8 9

*For usage in -35°C ~ -20°C enviroment, please refer to www.hytronik.com/download
->knowledge ->Microwave Sensors - Precautions for Product Installation and Operation
point 4) for more information.