Table 5 describes the User Menu items and supplies the factory defaults. (Factory default settings shown in bold.)
t
aBLe
5: u
Ser
m
enu
User Menu
Setting Options
Menu Tasks & Explanations
STC Wire
Connections
CT 0 (OFF)
CLOSE TIMER
0 = (OFF) Timer disabled
1 second to 99 seconds
The Close Timer assigns how many seconds before
the open gate initiates closure. It provides a security
precaution in case a CLOSE pulse is missed.
Keep the setting at 0 if a hard-wired, push-button
control device is being used. Refer to HC.
NOTE:
When the Hold to Close is set to 1 or more
seconds, the Close Timer display does not appear
and HC 1 becomes the User Menu entry display.
Not applicable (N/A)
HC 0 (OFF)
HOLD TO CLOSE
0 = off
1 = on
Set to 0 to produce a gate closure when a momentary
signal is transmitted.
Set to 1 if a constant hold to close signal, such as a
push button control, is being used. A setting of 1 also
deactivates the automatic close timer and causes its
menu to disappear. The Hold to Close replaces the
Close Timer display as the User Menu entry display.
NOTE:
To comply with UL 325 Type D protection,
set HC to 1. Type D UL 325 compliance means no
automatic closing device, such as a timer, loop sensor,
or similar device shall not be employed.
COM
Close
HO (OFF)
HOLD TO OPEN
0 = off
1 = on
Similar to Hold to Close, but configures the Open
inputs for a constant-hold function.
0 = Momentary open signal
1 = Constant hold open push button required
To comply with UL 325 Type D protection, you must
set HO to 1.
COM
Open
AP 0
AC LOSS
0 = UPS FAIL OPEN
1 = UPS FAIL CLOSE
2 = AUTO OPEN
3 = NO CLOSE TIMER
This menu item only appears if the operator is DC
powered. The setting configures how the gate
functions when AC power fails. For more information,
refer to the supplemental documentation.
COM
Terminal #21
UPS Terminal strip 24
VDC to control box
power disconnect
switch - and +
RO 0 (OFF)
RADIO OPEN/CLOSE
0 = off
1 = on
A setting of zero, configures radio input for open only.
Setting 1 adds the capability for radio input to close
the gate, but only when it is fully open.
COM
RADIO Open
BF 2 (ON 2 SEC)
WARN BEFORE OPER
0 = off
1 = warning buzzer on
throughout gate travel
2 = warning buzzer on for
2 seconds of gate travel
3 = warning buzzer on
during gate travel
Controls the warn-before-operate buzzer and can be
configured three ways:
Set to 0: Buzzer is disabled. The buzzer will still beep
if alerts, faults, errors, or entrapment occur.
Set to 1: Buzzer beeps for 3 seconds before gate
moves and continues through entire length of travel.
Set to 2: Buzzer beeps for 3s before gate moves and
continues for 2s of travel.
Set to 3:
Available on barrier operators only and
UC 4 if sensor inputs set to 1 “NOT USED”
.*
Buzzer beeps when gate starts to move and continues
throughout gate travel.
NOTE:
* Gate operators or replacement boards
manufactured in 2016 or later.
Not applicable (N/A)
Summary of Contents for HSG80F
Page 2: ...www SecureOpeners com 800 878 7829 Sales SecureOpeners com...
Page 14: ...Page intentionally left blank xiv MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 36: ...Page intentionally left blank 22 MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 124: ...110 MX3636 01 Rev D HydraSwing Programming Operations 2018 Page intentionally left blank...
Page 136: ...122 MX3636 01 Rev D HydraSwing Programming Operations 2018...