Inherent Entrapment Sensor System – Hydraulic Operators (IES)
The IES sensor:
• Is a normally closed pressure switch on the pump manifold
•
Senses fluid flow. High pressure spikes above pressure relief valve setting trigger gate obstruction
notification
•
Ignores first second of operation to preclude false trips due to starting pressure spike
An open contact:
• During gate movement signals the Smart Touch Controller to place gate operator into SAFE mode
• While the gate is not operating will generate ERROR 2 (ERR2) - disconnected IES
NOTE:
A second open contact, in either direction of travel, will lock the gate operator and ENTRAPMENT
MODE (ENTR) appears on the display.
t
He
i
nHerent
e
ntrapment
S
enSOr
(ieS)
The IES on HySecurity gate operators is an entrapment sensor that is required by UL 325 as a Type “A”
detection sensor. It is tripped through software programming OR hydraulic pressure settings. It does not
function solely on its own accord and must be connected to the Smart Touch Controller. The sensitivity and
response of the IES when tripped is factory set, but can be adjusted through the Installer Menu items:
• SE (Inherent Sensor sensitivity)
• SS (Inherent Sensor function)
• SR (IES reverse to open)
Smart Touch Controller™ – Installer Menu Functions for IES
Installer Menu
Display Code
Setting Options
(Bold – Factory Settings)
Description
SE 2
IES SENSITIVITY
1 = max. sensitivity
2 = Default setting
9 = least sensitivity
Adjusts the sensitivity of the internal inherent entrapment sensor
(IES). Available settings are 1 to 9 with 9 being the least sensitive.
HySecurity strongly recommends that you avoid setting the IES
sensitivity higher than 6.
Note:
Adjust pressure relief valve on hydraulic operators for security
and gate impact purposes prior to changing IES sensitivity. Refer to
the operator’s manual for steps involved in adjusting the pressure
relief valve setting.
SS 0 (OFF)
IES STOP ONLY
0 = stop, reverse for 2s
1 = stop only
A setting of 0, stops the gate and then reverses its direction of travel
for 2 seconds. To stop gate travel with no reversal, the optional
setting 1 can be selected if the gate operator is at a
Usage Class IV
site and assigned a UC 4 classification.
SR 0 (FULL OPEN)
REVERSAL LOGIC
0 = IES reverses fully open
1 = Two second reversal only
Setting of SR 0 causes the gate to reopen fully if triggered while
closing. With a setting of 1, if the inherent sensor is triggered, the
default setting reverses the gate travel for a 2-second duration.
30
MX3636-01 Rev. D
HydraSwing Programming & Operations
© 2018
Summary of Contents for HSG80F
Page 2: ...www SecureOpeners com 800 878 7829 Sales SecureOpeners com...
Page 14: ...Page intentionally left blank xiv MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 36: ...Page intentionally left blank 22 MX3636 01 Rev D HydraSwing Programming Operations 2018...
Page 124: ...110 MX3636 01 Rev D HydraSwing Programming Operations 2018 Page intentionally left blank...
Page 136: ...122 MX3636 01 Rev D HydraSwing Programming Operations 2018...