Troubleshooting for Fault Codes
3
62
810430
Troubleshooting Guide
Powermax65/85/105 SYNC
Generator considerations
If a fault occurs while you are using a generator, it is possible that doing a quick restart does
not remove the fault condition. Instead, set the power switch on the plasma power supply to
OFF (
O
) and wait approximately 1 minute before setting the power switch to ON (
I
).
Problems with input line voltage (fault codes 0-13-0, 0-60-
n
, and 0-61-0) can occur more
frequently with some generators. If you consistently see these fault codes, you can
temporarily set the
GEN
setting to on. This setting is on the Feature Configuration screen
(
FEATURE CONFIG
).
Hypertherm recommends that only experienced operators
change this setting.
This setting decreases the system’s sensitivity to changes in current
and voltage from incoming power.
Make sure that you set the
GEN
field to off when you are not using a generator.
If you continue to have problems with input line voltage, disconnect the plasma power
supply from the generator, and connect it to a power receptacle with sufficient power.
Refer to the
Powermax65/85/105 SYNC Operator Manual
(810470) for generator
specifications.