InstallatIon
3-50
HPR400XD Auto Gas –
806160
Power requirements
general
All switches, slow-blow fuses and power cables are customer-supplied and must be chosen as outlined by applicable
national and local electrical codes. Installation must be performed by a licensed electrician. Use a separate, primary, line
disconnect switch for the power supply. Recommendations on fuse and circuit breaker sizing are listed below, however
actual sizes required will vary based on individual site electrical line conditions (including but not limited to: source
impedance, line impedance, and line voltage fluctuation), product inrush characteristics, and regulatory requirements.
The main feed protection device (circuit breaker or fuse) must be sized to handle all branch-feed loads for both inrush
and steady-state current. The power supply must be wired into one of the branch-feed circuits. The power supply has a
steady-state current listed in the table below.
Use a motor-start circuit breaker or equivalent if time delay high inrush fuses are not permitted by local and national
codes. Time delay fuses and circuit breakers must be capable of withstanding inrush current that is up to 30 times the
rated input current (FLA) for 0.01 seconds and up to 12 times the rated input current (FLA) for 0.1 seconds.
Note: Cable AWG recommendations taken from table 310-16 of the National Electric Code handbook (USA).
Input voltage Phase
Rated
input current (FlA)
@ 80 kw output
Recommended
time delay,
high inrush
fuse size
Recommended cable size for 15 m
(50 ft) maximum length
Rated for 90°c (194°F)
200/208 VAc
3
262/252 amps
325 amps
235 mm
2
(350 MCM)
220 VAc
3
238 amps
300 amps
201.1 mm
2
(300 MCM)
240 VAc
3
219 amps
275 amps
167.5 mm
2
(250 MCM)
380 VAc
3
138 amps
175 amps
67.5 mm
2
(2/0 AWG)
400 VAc
3
131 amps
175 amps
67.5 mm
2
(2/0 AWG)
440 VAc
3
120 amps
150 amps
53.5 mm
2
(1 AWG)
480 VAc
3
110 amps
150 amps
53.5 mm
2
(1 AWG)
600 VAc
3
88 amps
110 amps
26.7 mm
2
(3 AWG)
Summary of Contents for HyPerformance HPR400XD
Page 1: ...HyPerformance Plasma HPR400XD Auto gas Instruction manual 806160 Revision 4 ...
Page 26: ...Specifications 2 2 HPR400XD Auto Gas 806160 ...
Page 48: ...Installation 3 10 HPR400XD Auto Gas 806160 ...
Page 53: ...Installation HPR400XD Auto Gas 806160 3 15 Horizontal RHF mounting Vertical RHF mounting ...
Page 57: ...Installation HPR400XD Auto Gas 806160 3 19 This page is blank intentionally ...
Page 65: ...Installation HPR400XD Auto Gas 806160 3 27 7 8 8 7 ...
Page 100: ...Installation 3 62 HPR400XD Auto Gas 806160 ...
Page 107: ...Operation HPR400XD Auto Gas 806160 4 7 Diagnostic screen ...
Page 108: ...Operation 4 8 HPR400XD Auto Gas 806160 Test screen ...
Page 109: ...Operation HPR400XD Auto Gas 806160 4 9 Cut chart screen ...
Page 197: ...Operation HPR400XD Auto Gas 806160 4 97 ...
Page 287: ...7 4 HPR400XD Auto Gas 806160 Discrete output functionality ...
Page 347: ...Appendix B CNC Interface Protocol b 28 HPR400XD Auto Gas 806160 ...
Page 355: ...4 HPR400XD Auto Gas 806160 ...