Page 30
9.4 Maintenance steps
9.4.1 Removal of the steam cylinder
»
Drain cylinder water making use of
blow-down pump.
»
Disconnect unit from power supply-
and secure against reconnection.
»
Shut off the water supply.
»
Wait 10 minutes so that the possibly
hot cylinder can cool down.
»
Check the temperature by carefully
approaching it with your hand, do not
touch the cylinder if the rest heat
should be too strong.
»
Remove the steam hose from the
steam hose adapter.
»
Separate connector halves.
»
Lift steam the cylinder from the cylin-
der base.
9.4.2 Cylinder cleaning / O-ring
replacement
For cleaning, mechanical removal of the
deposits is usually sufficient.
Risk of eye injuries!
The clips that fix the steam cylinder halves
have sharp edges and can jump off during
dismantling.
Eye injuries are possible.
Wear proper PPE (Personal Protection Equip-
ment)!
»
Remove the cylinder flange clamps.
CAUTION
!