6.3.1
Feed from Holding Tank
If a holding tank will be used to supply water, the „option sole-
noid valve 0-10bar” must be ordered. Make sure that the feed
height is at least 0.5m/19.7inch. If the height is less than 0.5m/
19.7inch, insert a feed pump or install the humidifier lower if pos-
sible.
6.4
Water Treatment
For water treatment system specifications, use the following
table.
The figures below assume that the humidifier has been running
for 24 hours at 100% output.
HeaterLine Max. Water Consump-
tion in over 24 h [l]
6
166
9
248
12
331
18
497
24
662
30
828
36
994
45
1242
option: solenoid
valve 0-10 bar
/19.7inch
/19.7inch