Page 36
6.2.1.2
Exhaust Fan D1 (Operating Mode)
Possible Settings: - Automatic
- On (Continuous Operation)
- Off
Automatic
At this setting, fan operation is a function of the temperature in the
steam bath. The control switches the exhaust fan on when the desired
temperature is reached, and switches it off again when the tempera-
ture falls below the set value minus hysteresis.
Also see Parameters “Steam Bath °C set value (G2) and “Hysteresis
fan (G3). If the fan is control-activated, the letter
F
is shown on the dis-
play.
On (Continuous Operation)
When in continuous operation, the fan runs independently of the tem-
perature in the steam bath. In this setting, you use the control switch to
simultaneously switch the fan and the steam generator on and off.
Off
The exhaust fan is deactivated on this setting.
6.2.1.3
Essence D2 (Operating Mode)
Possible Settings: - On
- Off
On
If Parameter “Essence Injection” (D2) is programmed to “
On
”, essence
is delivered according to the programmed Interval Time Essence
Injection (G5) und Time Essence Injection (G4). At factory settings, the
essence interval period is 5 minutes and the essence injection duration
is 2 seconds.
Off
When Parameter “Essence Injector” (D2) is programmed to “deacti-
vated,” no essence is added to the steam.