hyfire HFW-MA-05 Instructions Download Page 1

 

OVERVIEW

 

 

This detector model samples the air and the environmental temperature in the protected area. An alarm condition is raised when the detected 

environmental smoke quantity, the temperature level or the thermal variation rate exceeds the alarm threshold.

 

 

COMPATIBILITY

 

 

This detector is compatible only with wireless systems based on the Sagittarius protocol.

 

For more specific information concerning compatibility refer to your fire security system supplier.

 

 

INSTALLATION 

-

 IMPORTANT NOTES

 

 

For detector spacing, placement and special applications refer to your specific national standards.

 

Mount  the  detector  as  far  as  possible  from  metal  objects,  metal  doors,  metal  window  openings,  etc.  as  well  as  cable  conductors,  cables 

(especially from computers), otherwise the operating distance may greatly drop. The detector must NOT be installed near electronic devices 

and computer equipment that can interfere with its wireless link quality.

 

 

This detector must be installed according precisely to the procedures described in this manual.

 

 

Test this detector after installation.

 

 

BEFORE INSTALLING THE DETECTOR

 

 

1)

 

Extract the batteries cover from the back of the detector.

 

2)

 

Power

-

up the detector removing the isolating tab in the battery

 

     housing.  LED indicators signal 

Power up

”.

 

3)

 

Link the detector to the Sagittarius wireless system (

LINKING

).

 

4)

 

Check the 

WIRELESS LINK QUALITY

.

 

5)

 

SELECT A GOOD LOCATION FOR THE DETECTOR

.

 

6)

 

Tag device

s loop and address data (

IDENTIFICATION

).

 

7)

 

Fix the detector supporting base to the wall (

BASE INSTALLATION

).

 

 

LED INDICATORS

 

 

Picture 1: provide visual indication for functional conditions and battery levels as indicated in 

table 1.

 

 

 

Hyfire Wireless Fire Solutions Limited 

-

 Unit B12a, Holly Farm Business Park, Honiley, 

 

Warwickshire, CV8 1NP 

-

 United Kingdom

 

www.hyfirewireless.com

 

HFW

-

MA

-

05

 

BI

-

DIRECTIONAL WIRELESS ADDRESSABLE  MULTICRITERIA 

 

DETECTOR WITH VARIABLE SENSITIVITY

 

LED INDICATORS

 

Picture 1

 

928m/02

 

Table 1

 

Detector

s status

 

LEDs indication

 

Power up

 

1 second 

GREEN

, then 4 X 0.5 second 

RED 

blink

 

Linking to the system

 

Blinking 

GREEN 

until linking is completed 

 

Link failure

 

RED 

on (continuous)

 

Normal condition

 

LEDs off

 

Alarm

 

Blinking 

RED

: 0.5 second on and 0.5 second off

 

Battery 1 fault

 

0.1 second 

ORANGE 

blink, then 5 seconds off

 

Battery 2 fault

 

0.1 second 

GREEN

 blink, then 5 seconds off 

 

Both batteries fault

 

0.1 second 

ORANGE,

 then 5 seconds off

 

0.1 second 

GREEN,

 then 5 seconds off

 

Other fault

 

sequential 

ORANGE 

GREEN 

0.5 second blinking

 

Tamper

 

LEDs off

 

Lost link with wire to 
wireless translator / 
wireless expander

 

LEDs off

 

Type 1 Test Mode

 

Blinking 

GREEN

 every 1 second for 1 minute

 

Type 2 Test Mode

 

GREEN

 on (continuous) for 30 minutes

 

Reviews: