hyfire HFW-CEM-02 Quick Start Manual Download Page 1

HFW

-

CEM

-

02

 

WIRELESS CONVENTIONAL SYSTEM 

EXPANDER MODULE

 

STERLING SAFETY SYSTEMS

 

-

 Unit B12a, Holly Farm Business Park, Honiley, Warwickshire, 

CV81NP

 

www.sterlingsafety.co.uk

 

Picture 1 

-

 Device overview

 

Picture 3 

-

 Breakable holes for cable entry

 

Picture 2 

-

 Wall fixing screw holes, their distances 

from each other and the maximum allowed screw 

diameter

 

Picture 6 & 7 

-

 Power supply unit example schemes

 

Picture 11 

-

 Convention-

al line wiring (zone line 

EOL resistor inside of 

the device)

 

MAIN MONITORING

 

BACKUP MONITORING

 

Picture 8 

-

 Power 

supply monitoring 

lines wiring 

 

Picture 4 

-

 An example of a 

conventional 

-

 wireless 

system

 

DEVICE WIRING 

-

 POWER SUPPLY

 

 

The conventional system expander module must be power 

supplied either:

 

 

-

 directly by the control panel or

 

 

-

 from an external power source or

 

 

-

 from an external power source with a power backup unit.

 

 

Use the scheme at the right for connecting the power supply to 

the device.

 

 

This terminal wiring scheme is always applied.

 

 

If you want to use an external power source with a power 

backup unit, two additional module

s terminal blocks come in 

use: 

MAIN MONITORING

” 

and 

BACKUP MONITORING

”.

 

 

MAIN MONITORING

” 

is a terminal that supervises the main 

power supply of an external power supply unit.

 

 

BACKUP MONITORING

” 

is a terminal that supervises the backup power supply of an external power supply unit.

 

 

Let

s have two examples of power supply units:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAIN MONITORING

” 

and 

BACKUP MONITORING

” 

lines will be connected to the module as in the following scheme:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEVICE WIRING 

-

 CONVENTIONAL ZONE LINE

 

 

In order to connect this device to the conventional zone line, two types of schemes can be used, depending on the positioning of the expand-

er module on the line:

 

 

-

 the expander module is positioned at the beginning or in the middle of the zone line (conventional devices follow the device  on the line or 

are positioned before and after it); therefore the zone line EOL resistor must be fitted externally as is normally done, but not into the device

terminal blocks:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 the expander module is positioned at the end of the zone line (all conventional devices are positioned before it); therefore  the zone line 

EOL resistor must be fitted to the device

s terminals and not externally as normally is done.

 

Picture 10 

-

 Convention-

al line wiring (zone line 

EOL resistor outside of 

the device)

 

[email protected]

 

L20

-

SGCWE

-

1400 (vA.3)

 

 

928r/01

 

 

 

 

 

 

 

 

GENERAL DESCRIPTION

 

 

The  wireless  conventional  system  expander  module  is  a  device  permitting  to  add  a  wireless  sub

-

system  to  a  conventional  fire  security 

installation. This device is connected directly to the conventional control panel zone line and is actually part of it. This device allows wireless 

sounders silencing by being controlled by the control panel

s sounder output line.

 

 

Note: The latest release of the wireless system configuration software is available from the manufacturer

s website.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHAT TO CHECK BEFORE INSTALLATION

 

 

Before  installing  the  conventional  system  expander  module 

check these following items:

 

 

 

 

 

 

 

 

 

-

 This device must be installed following your national and / or international codes of practice and standards: check them before performing 

the installation of this device.

 

 

-

 This device is compatible with most of the conventional control panels; check that the control panel is equipped with a power supply output 

through which you can, if desired, power the conventional system expander module; check if the panel is provided with a sounder output; 

check that control panel

s specifications are suitable; for all this, consult your control panel

s documentation or consult your control panel

supplier for more information.

 

 

DEVICE POSITIONING FOR RADIO COMMUNICATION PERFORMANCE AND STABILITY

 

 

The conventional expander module must have a good radio communication with its wireless system

s child devices. In order to achieve this, 

before positioning it and installing it, apply scrupulously the following points:

 

 

-

 Avoid installing the module close to:

 

 

· equipment using large amounts of electrical current

 

 

 

 

 

 

· large metal objects, structures or metal ceiling structures

 

 

 

 

 

 

· fluorescent lighting fixings

 

 

 

 

 

 

· computers, their cabling and network cabling.

 

 

-

 If there are other wireless translators or wireless modules, keep a distance between them of at least 2 meters. In general every installed 

radio device (child devices included) must have a minimum distance of at least 2 meters from each other.

 

-

 It is recommended to install the conventional expander at a height from the floor of at least 2 

-

 2.5 meters.

 

-

 Install the conventional expander perfectly flat on the wall.

 

-

 The conventional expander must be installed perfectly straight on the wall; this means that the antenna under the device must be perpen-

dicular to the floor and the antenna on the right of the device must be parallel to the floor.

 

Environmental  parameters  (temperature,  humidity  and  so  on)  must  be  in  the  ranges  specified  in  the  conventional  expander

s  technical 

specifications, which can be found at the beginning of this manual; this point applies, obviously, to all other wireless devices.

 

-

 After having installed the conventional expander, make sure that its child devices (sensors, call points, etc.) are reached by a good, strong 

signal (refer to the single device

s manuals) in their position of installation.

 

Radio transmission ranges for the conventional expander can found in the technical specifications at the beginning of this manual.

 

-

 Use the personal computer

Wirelex

-

fire

 software for configuring and administering the system.

 

 

PLACEMENT AND FIXING

 

 

The conventional system expander module

s lodgement box is designed with four 20 mm breakable, 

knock

-

out

” 

entry holes (two at the top 

and two on the upper side of the rear of the box), allowing sealed, cable gland fitted, cables to be connected to the device.

 

To place and fix the module perform in sequence the following steps:

 

 

-

 Find a suitable location for the device

s box.

 

-

 Prepare the cable openings on the box.

 

-

 Securely and adequately fix the device

s box to the wall with adequate screws.

 

-

 Fit the cable

s gland (or glands) into the 

knocked out

” 

device box

s cable entry; check gland

s IP rating: it must be equal or greater than the 

IP rating of the expander module: see the TECHNICAL SPECIFICATIONS table.

 

-

 Feed the cables into the box, giving them sufficient length for a secure connection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRING CONNECTIONS

 

 

The conventional system expander module

s wiring phase of the installation has the following objectives:

 

 

-

 Connect the power supply cables (either from the control panel of from an independent source).

 

 

-

 Connect main and backup power supply monitoring inputs (optional).

 

 

-

 Connect the conventional zone line.

 

 

-

 Connect the control panel

s sounder output (optional).

 

 

-

 Install the end of line (EOL) resistors required as specified in this manual; their values must be chosen according to the control panel

specification and literature.

 

 

WIRING WARNINGS

 

 

Three warnings about wiring:

 

 

-

 Perform any wiring operation with the power supply source and the control panel inactive.

 

 

-

 Electrostatic sensitive device: observe precautions when handling and making connections.

 

 

-

 Connections to the terminals are polarity sensitive, thus, please, check them by referring to the wiring instructions of this manual.

 

 

IMPORTANT NOTE

 

 

Check and apply the 

ZONE ALARM EOL

” 

and the 

CHECKING THE POSITIONING OF THE ELECTICAL BRIDGES

“ 

paragraphs before 

using the expander module.

 

TECHNICAL SPECIFICATIONS *

 

Communication range between expander and 

wireless devices

 

200 meters (in open space)

 

Operating frequency

 

868.15 MHz –

 869.85 

Mhz

 

Modulation type

 

FSK

 

Operating frequency channels

 

7

 

Radiated power

 

5 dBm (3 mW)

 

Power supply voltage range 

**

 

9 VDC 

-

 30 VDC

 

12 VDC typical

 

Power supply lower fault threshold

 

9 VDC

 

Conventional zone line applied voltage

 

Same as device

s power  

supply applied voltage

 

Sounder

s line maximum voltage

 

27 VDC

 

Expander maximum current consumption

 

60 mA at 12 VDC (alarm)

 

Operating temperature range

 

-

30 °C to +50 °C

 

Dimensions (without antennas)

 

120 mm x 160 mm x 51 mm

 

Weight

 

330 grams

 

Ingress protection rating

 

IP 51C

 

Required programming software

 

Wirelex

-

Fire

” 

revision 5.0 

and successive

 

+

 

POWER SUPPLY

 

Picture 5 

-

 Power 

supply connection 

scheme

 

96 mm

 

146 mm

 

4 mm

 

* Check latest version of document TDS

-

SGCWE for further data, obtainable 

from your supplier.

 

Picture 9 

-

 Ferrite 

ring installation

 

WARNING!

 

 

POWER SUPPLY 

-

” 

AND 

POWER SUPPLY 

+” 

WIRES MUST PASS INTO 

THE SUPPLIED FERRITE RING.

 

IMPORTANT:  Please  note  that  with  this  wiring 

arrangement,  if  a  fault  occurs  on  the  wireless 

sub

-

system,  the  remaining  conventional  zone 

after  the  expander  may  be  isolated  until  the 

fault  has  been  cleared.  This  will  apply  unless 

each detector on the circuit is equipped with a 

Schottky  diode  that  the  panel  can  use  for 

continuity purposes.

 

 

Please  refer  to  your  applicable  codes  of  prac-

tice  and  to  your  conventional  control  panel 

documentation.

 

* * 

Power source type ES1, PS2

 