Hydro-Air P-38
Advanced Operation
pH / ORP Analyzer
15
6.3.
Relay B Settings
DISPLAY
FUNCTIONS
Example:
If an alkali dosing pump is required
to run at pH 4 and to stop at pH 10,
then
set
Run=04.00pH
and
Off=10.00pH
Status:
Enable / Disable Relay B
Run:
Set point value to energize Relay B
pH
: 0.00 to 14.00pH
ORP
: -2000 to 2000mV
Off:
Set point value to deenergize Relay B
pH
: 0.00 to 14.00pH
ORP
: -2000 to 2000mV
6.4.
Measurement Settings
DISPLAY
FUNCTIONS
Mode:
Set the parameter to measure
Parameters: pH / ORP
Offset:
Parameter value adjustment
pH
: -1.00 to +1.00pH
ORP
: -100 to +100mV