Error analysis / remedy
MCS1xxx /-T005
en(us)
Page 52 /
68
BeWa MCS1xxx-T005 4668567a en-us 2022-06-14.docx
2022-06-14
Parameter:
TYPE
FE = switching output 1
NFE = switching output 2
NUM
Number of pulses
START
Start of function test
Factory setting:
TYPE
FE
NUM
5
ALARM – Setting limit values
Function:
Set limit values.
The signal is active for 30 seconds after exceeding a
limit value. The alarm indicates that the set limit value
has been exceeded and is not necessarily due to any
damage to the monitored system.
Parameter:
A – Minute (min)
PERIOD 10 … 180
LIMIT
5 … 2
32
B – Hours (h)
PERIOD 2 … 72
LIMIT
20 … 2
32
C – Days (d)
PERIOD 3 … 30
LIMIT
100 … 2
32
Factory setting:
A
PERIOD 30
LIMIT
20
B
PERIOD 24
LIMIT
100
C
PERIOD 7
LIMIT
500
CANCEL - cancel without saving
Parameter:
None
SAVE - Save changes
Parameter:
None
Error analysis / remedy
If the Device Ready signal does not indicate that the device is ready for use,
proceed as follows: