MCS 1000 Series
Switching output "Device Ready"
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 46 / 76
BeWa MCS1000 3435427f V130 en-us 2012-06-15.doc
2012-06-15
Switching output "Device Ready"
When "Device Ready" is set, the buzzer signal of the ferromagnetic and non-
ferromagnetic particles is emitted on the switching output S1.
The signal indicating that the MCS is ready for use is emitted on the switching
output S2. The signal is always emitted in the same way regardless of the switching
logic "active low" or "active high".
Note that after the sensor has been switched on and after voltage has returned after
an interruption, a start-up phase of ~ 70 seconds is necessary before the signal can
be evaluated.
After that, the switching output "Device Ready" goes to permanent "low" potential.
0 V
0
U
M1/2
U
t
70 s