MCS 1000 Series
Switching logic "active low"
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 42 / 76
BeWa MCS1000 3435427f V130 en-us 2012-06-15.doc
2012-06-15
Switching logic "active low"
Both switching outputs emit a currentless signal when a particle is detected.
You can set the duration of the signal between 5 and 200 ms.
This value is factory set to 7 ms.
The signal gives no indication of the shape and size of the particles.
Switching on sensors
Note that after the sensor has been switched on or after voltage has returned, a
start-up phase of ~ 70 seconds is necessary before the first measurement can be
made.
Example: Operation - 1 particle detected
0 V
0
U
t
70 s
U
M1/2
Δ
t