Unit setup/connection
LVU-CD-10
en(us)
Page 26 / 52
BeWa LVU-CD-10 Eco 4067271 en-us 2016-01-08.doc
2016-01-08
Checking the water connection / water reservoir
Check the water collecting tank (4) for damage. Completely empty the water
reservoir via the water drain plug (4.1).
The separated water can contain some parts of fuel.
Dispose of the water-fuel mixture in an environmentally
friendly manner.
NOTICE
Excess pressure at the water outlet
The filteration unit will be damaged
►
Guide the water outlet into a depressurized reservoir.
Electrical connection
The filtration unit has a connector cable with a power plug.
DANGER
Exposed electric terminals in the terminal
box of the electric motor
Danger of fatal injury due to electric shock
►
Any work involving the electrical system may
only be done by a properly trained, certified
electrician.
Unwind the connector cable fully. Plug the power plug into a suitable,
earthed, protected power outlet. Match the specifications for the power
supply and frequency on the unit with the network specifications.
The filtration unit has a thermal motor protection switch to protect it from
electrical overload.
Summary of Contents for LVU-CD-10
Page 51: ......