ContaminationSensor CS 1000
CS1000 Measurement mode
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 29 / 108
BeWa CS1000 3247149p 240 en-us 2011-02-11.doc
2011-02-11
Mode M4: Filter to continuously monitor cleanliness class
Application:
Control of stationary offline filtration unit
Data output:
Display & RS485 & analog output & switching output
Purpose:
Establish continuous monitoring of cleanliness class between
min./max. limit values.
Function:
Controlling a filter unit, continuous measurement of solid
contamination.
If min./max. limit values are pre-programmed, the CS switches
the pump on/off to keep cleanliness within the limit value
range.
T 1
Once the target cleanliness has been reached (5x undershooting the TARGET), the
set test cycle time in minutes appears on the display. The test cycle time expires.
After the test cycle time has elapsed, the switching output is closed and a
measurement is started. If the result is still below the TARGET cleanliness, the test
cycle time begins again.
Mode "SINGLE" measurement
Application: Stand-alone
sensor
Data output:
Display & RS485 & analog output
Purpose:
Perform a single measurement and "stop" the result.
Function:
Single measurement of solid contamination without switching
functions
When Single mode is selected in the PowerUp menu, the display jumps directly to
the following message after switching to the Measuring menu or after switching the
CS on:
The CS begins with individual
measurement after the message has
been confirmed by pressing
o.k.
.
Use the
Esc
button to return the
sensor one level higher in the menu
structure.
START?