TransformerCare Unit
TCU in operation
HYDAC FILTER SYSTEMS GMBH
en
Page 36 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05
Setting EDS switchpoints for the alarm and stopping pressure
The EDS has two switch outputs. You can set one switchpoint and one hysteresis
for every switching output.
The respective output switches when the set switchpoint has been reached and
switches back when the switch-back point has been fallen short of. The switch-back
point is always determined by the set hysteresis (switch-back point = switchpoint
minus hysteresis).
"
SP1
", "
SP2
"
= Switchpoint 1 or 2
"
HY1
", "
HY2
"
= Hysteresis 1 or 2
Alarm pressure
=
SP2
Stop pressure
=
SP1
We recommend the following for setting the alarm pressure and the stop pressure:
Alarm pressure
=
SP2
The alarm pressure should be ~ 20 % above the
currently displayed pressure (upper pressure).
At least 20 mbar higher than the actual pressure.
Stop pressure
=
SP1
600 mbar.
EDS factory settings
Designation
Value
Alarm pressure
SP2
= 500
Alarm pressure hysteresis
HY2
= 10
Stop pressure
SP1
= 600
Hysteresis stopping pressure
HY1
= 10