10.1 Parameterization by means of the IO-Link Master
The temperature sensor can be parameterized via the device keys or via the IO-Link interface
by means of any IO-Link compatible master configuration tool (according IO specifications
V1.1).
10.2 Parameterization by means of HYDAC programming adapter ZBE P1-000
(Connection with standard cable)
Sensor
1
ZBE P1
2
3
4
5
1
2
3
4
5
L+
L-
USB
PC
Q1
10.3 Parameterization by means of HYDAC portable measuring unit HMG 4000
Connection via standard cable to an IO-Link female connector; detailed information can be
taken from the HMG 4000 operation manual.
10.4 Adjustable parameters (read write)
Interlock for unauthorized device access (Index 12)
o
Parameter (write) access (Subindex 1):
Unlocked (False)
Locked (True)
o
Data retention (Subindex 2)
User-specific mark (Index 24)
Function-specific mark (Index 25)
Site specific mark (Index 26)
Parameter SSC1 (Index 60) and SSC2 (Index 62):
each
o
SP1 (Subindex 1): upper setting value in °C, adjustable up to 200 % of the
measuring range with 1 decimal place.
o
SP2 (Subindex 2): lower setting value in °C, adjustable up to 200 % of the
measuring range with 1 decimal place.
Configuration of SSC1 (Index 61) and SSC2 (Index 63)
,
each
o
Logic (Subindex 1): switching logic: Default: High active
-
If "High Active":
SSC = 0: OFF
SSC = 1: ON
- If "Low Active":
SSC = 0: ON
SSC = 1: OFF
Data retention (Subindex 2) is available for compatibility reasons and
should always be set to "false" in order to prevent from unexpected
behaviour when storing data between the master and the device.