HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 (Printed in U.S.A.)
MERCHANDISER ELECTRICAL DATA
Merchandiser data sheets are attached to the front
of this manual. The data sheets provide case elec-
trical data, electrical schematics, parts lists and
performance data. Refer to the merchandiser data
sheets and case serial plate for electrical informa-
tion.
ELECTRICAL CONNECTIONS
All wiring must be in compliance with NEC and
local codes. All electrical connections are to be
made in the electrical raceway or
Handy Box
.
FIELD WIRING
Field wiring must be sized for component amperes
stamped on the serial plate. Actual ampere draw
may be less than specified. Field wiring from the
refrigeration control panel to the merchandisers is
required for defrost termination thermostats and for
optional refrigeration thermostats. When multiple
merchandisers are on the same defrost circuit, the
defrost termination thermostats are wired in series.
ALWAYS CHECK THE SERIAL PLATE FOR COMPO
-
NENT AMPERES
.
ELECTRICIAN NOTE:
Use copper conductor wire only.
CASE MUST BE GROUNDED
Optional
Refrigeration
Thermostat
12 In. (305 mm)
Optional Refrigeration
Thermostat Bulb
Standard Defrost
Termination
Thermostat
6 Ft (1829 mm)
5 Ft (1524 mm)