Absolute Encoder AMP(H) 41
AMP(H)41_MANUAL-en_R11 - 2019-03-28
89
14
Technical Data
14.1
Safety
Functional safety
EN 61508 Part 1-7:2010
Safety Integrity Level (SIL): CL3
EN ISO 13849-1:2008/AC:2009
Performance Level (PL): e
Startup time
Time between POWER-UP and safe position output
Overall system
5 s
PFH, „High demand“ operating
mode
7.88 * 10
–10
1/h
PFD
av
(T
1
= 20 a)
6.71 * 10
–5
MTTF
d
high
98 a
* DC
avg
high
98 %
Internal process safety time
Time between occurrence of an F-Error and alarm
indication
Overall system
10 ms
Process safety angle
Angle between error occurrence and alarm indication
Via channel-internal self-diagnosis
± 100 °, in relation to the measuring system shaft
Through channel comparison
Parameterizable with iParameter
Window increments
T
1
proof test
20 years
* The assessment occurred in accordance with Note 2 on Table 6 of EN ISO 13849-1.
14.2
Electrical characteristics
14.2.1
General
Supply voltage
13…27 V DC acc. to IEC 60364-4-41, SELV/PELV
Feed
Single feed, but electrically separated internally by
means of two power supplies
Reverse polarity protection
Yes
Short-circuit protection
Yes, by internal 2 A safety fuse
Overvoltage protection
Yes, up to
≤
36 V DC
Current consumption without
load
< 150 mA at 24 V DC
Option HTL-Level, 13…27 V DC
Increased current consumption, see page 32