Service/maintenance
Chapter 7
OPERATION MANUAL
V2.2.0en/09.08.21//17.12
Unichiller® eo Desktop
75
Identify the position of the ventilation grille, usually located on the front. With some temperature
control units, the ventilation grilles on the side wall, rear or on the underside (table units) of the
temperature control unit.
PROCEDURE
Ventilation grille on the front/rear or on a side wall
Turn off the temperature control unit.
Disconnect the temperature control unit from the power supply.
Remove the ventilation grille to create unhindered access to the liquefier fins.
Clean the liquefier fins using suitable cleaning appliances. Observe the local regulations and
ambient conditions when selecting cleaning appliances.
Make sure the liquefier fins are not damaged or deformed as this will impair the air flow.
Re-mount the ventilation grille after cleaning work.
Connect the temperature control unit to the power supply.
Turn on the temperature control unit.
PROCEDURE
Ventilation grille on the underside (table-top units)
Cleaning of liquefier fins at the underside when the temperature control unit is filled
DAMAGE CAUSED BY THERMAL FLUID PENETRATING THE TEMPERATURE CONTROL UNIT
Empty the temperature control unit before cleaning the liquefier fins at the underside of the
temperature control unit.
Switch off the temperature control unit.
Disconnect the temperature control unit from the power supply.
Drain the thermal fluid from the temperature control unit.
→
Tilt the temperature control unit to remove the grille (if available) in front of the liquefier fins.
Clean the liquefier fins using suitable cleaning appliances. Observe the local regulations and
ambient conditions when selecting cleaning appliances.
Make sure the liquefier fins are not damaged or deformed as this will impair the air flow.
Re-mount the ventilation grille after cleaning work.
Connect the temperature control unit to the power supply.
Refill the temperature control unit with thermal fluid.
→
7.3.4
Clean hat-type strainer (dirt trap) (water-cooled temperature control unit)
Building’s isolating valves are not closed
PROPERTY DAMAGE CAUSED BY FLOODING OF ROOMS
Close the building’s isolating valves in the cooling water supply and return lines.
For table-top models, place a collection container below the
>Cooling water drain<
[15]. Ob-
serve the wiring diagram:
→
The strainer at the cooling water inlet must be inspected and cleaned on a regular basis, depend-
ing on water quality.
PROCEDURE
Table-top models:
Turn off the temperature control unit.
Disconnect the temperature control unit from the power supply.
Close the customer’s shut-off valves in the cooling water supply and return lines.
Place a collecting container below the
>Cooling water inlet<
[13].
Remove the cooling water supply line and take out the hat-type strainer for inspection and cleaning.
Clean the suction strainer under running water.
Following inspection/cleaning, reinsert the hat-type strainer and fasten the cooling water supply line.
Remove the collecting container from below the
>Cooling water inlet<
[13].