Service/maintenance
OPERATION MANUAL
Chapter 7
Minichiller®
V2.4.0en/09.08.21//1.30
48
Cooling*
Description
Maintenance
interval
Comment
Person re-
sponsible
A/W
Check the tempera-
ture control unit for
damage and stability
Every 12 months
or after a change
of location
–
Operating
company and /
or operators
W
Check the cooling
water quality
Every 12 months
Descale the cooling water circuit
as required. Documentation on
water quality is available at:
www.huber-online.com
Operating
company and /
or operators
A/W
Exchange safety-
relevant electric and
electromechanical
components
20 years
Have the exchange only carried
out by certified personnel (such as
Huber service engineers). Please
contact Customer Support.
→
Page
Operating
company
*A = Air cooling; W = Water cooling; U = Applicable only for Unistats
7.2.2
Replacing temperature control or coolant hoses
Replace defective temperature control and/or coolant hoses
before
turning on the temperature
control unit.
7.2.2.1
Replacing temperature control hoses
PROCEDURE
Drain the temperature control unit.
→
»Draining externally closed applications«
Replace defective temperature control hoses. Observe the proper disposal.
→
Page 15, section
»Proper disposal of resources and consumables«
Reconnect your external application.
→
»Connecting externally closed application«
Fill the temperature control unit with thermal fluid.
→
externally closed application«
Vent the temperature control unit.
→
»Filling and venting externally closed
Restart the temperature control unit in normal mode.
7.2.2.2
Replacing coolant hoses
PROCEDURE
Drain the cooling water.
→
Replace the defective coolant hoses. Follow the instructions for the proper disposal.
→
Page 15,
section
»Proper disposal of resources and consumables«
Reconnect the temperature control unit to the building’s cooling water supply.
→
Page 28, sec-
tion
»Temperature control units with water cooling«
Restart the temperature control unit in normal mode.
7.2.3
Clean liquefier fins (air-cooled temperature control unit)
Manual cleaning
RISK OF BEING CUT ON THE LIQUEFIER FINS
Wear suitable cut-resistant gloves for cleaning work.
Depending on the ambient conditions, use cleaning equipment such as vacuum cleaners and/or
a hand brush/brush. Follow the local regulations when cleaning. Do not clean the liquefier fins
in a clean room with items like a brush and do not use a vacuum cleaner without an extra-fine
particle filter.
Cleaning using pointed or sharp-edged tools
DAMAGE TO THE LIQUEFIER FINS
Clean the liquefier fins using suitable cleaning appliances.
Summary of Contents for MPC Minichiller 280
Page 1: ...MPC Minichiller...
Page 2: ......
Page 3: ...OPERATION MANUAL MPC Minichiller...
Page 4: ......
Page 10: ...OPERATION MANUAL Minichiller V2 4 0en 09 08 21 1 30 10...
Page 59: ...Annex Chapter 9 OPERATION MANUAL V2 4 0en 09 08 21 1 30 Minichiller 59 9 Annex...