  MP15 Jockey Pump Controller 

Publication 245-EN – November 2013 

 
System Set Point Definitions 

Set Point 

Definition 

Start Pressure 

If the system pressure is at or below this 

setting, and the HOA switch is in the Auto 

position, then the controller will start the 

pump. 

Range: 

0 – 600 PSI 

 

0 – 41.3 BAR

 

Stop Pressure 

When a low system pressure start occurs, 

the start condition will stay active until the 

system pressure rises to the stop pressure. 

Range:

 

1 – 600 PSI 

 

0.1 – 41.3 BAR

 

Start Delay 

This time setting delays the automatic start 

of the pump when a low system pressure 

condition occurs. 

Range: 

0 – 999 Seconds

 

Minimum Run Time 

The minimum time that the pump must run 

before an automatic stop. 

Range:

 

0 – 999 Seconds

 

Short Cycle Time 

Activates an alarm if an automatic start 

occurs within the configured time span since 

the last automatic stop.  This setting is used 

to determine if the 

Start Pressure

 and 

Stop 

Pressure

 set points need adjustments. 

Set to zero seconds to disable. 

Range:

 

0 – 999 Seconds

 

Short Cycle Reoccurrence 

The number of consecutive short cycles that 

must occur before the short cycle alarm is 

activated.  When the short cycle time span 

elapses, this counter is reset. 
This setting is used to prevent nuisance 

alarms. 

Summary of Contents for Metron MP15

Page 1: ...ration maintenance and system setup information for Metron Model MP15 Jockey Pump Controllers Section Page Introduction 2 Installation 3 Operation of the Controller 5 Operator Interface Device OID Use...

Page 2: ...ormal water pressure and prevent unnecessary cycling of the main fire pump s Approvals Metron MP15 controllers are listed by Underwriter s Laboratories Inc in accordance with UL508A Standard for Indus...

Page 3: ...d risk of SERIOUS INJURY or DEATH and to avoid damage to the controller READ THIS SECTION CAREFULLY If questions or concerns still exist contact the Metron factory for further clarification If work mu...

Page 4: ...he installer is responsible for ensuring no metallic foreign objects such as drilling chips etc fall inside the controller onto the electrical circuit Failure to observe this could result in damage to...

Page 5: ...may fluctuate slightly due to small leaks in the system The use of this small pump will eliminate frequent starting of the main pump The Jockey Pump Controller automatically starts the Jockey Pump Mo...

Page 6: ...erly installed all external connections have been made and the Motor Starter Protector is closed Manual Operation To manually start the jockey pump motor turn the HOA Selector to the Hand position Thi...

Page 7: ...ist of windows They are denoted onscreen with an arrow to the right of the text Set Points which display the set point name and its current value Use the EN T E R UP and DO WN buttons to navigate thro...

Page 8: ...sure HOA switch position and status of the pump If there is no user activity on the OID after five minutes the onscreen window will automatically return to the Home window Alarms and Events When there...

Page 9: ...ndow choose Log Out Note The Log Out menu item will not be displayed if the current user login status is not logged in Configuring System Set Points WARNING To configure the system set points place th...

Page 10: ...the UP and DO WN buttons to change the value of the current step b Use the EN T E R button to confirm with current step 3 When the current set point configuration is complete the next set point will...

Page 11: ...igation Tree Home Window System Set Points User Preferences Tech Screen USB Memory Stick About Window Calibrate Pressure Sensor Language Pressure Unit Screen Brightness Start Pressure Stop Pressure St...

Page 12: ...automatic start of the pump when a low system pressure condition occurs Range 0 999 Seconds Minimum Run Time The minimum time that the pump must run before an automatic stop Range 0 999 Seconds Short...

Page 13: ...mber 2013 Set Point Definition Language Selects the onscreen language Pressure Unit Selects the system pressure unit PSI or BAR Screen Brightness Adjusts the brightness of the screen backlight Calibra...

Page 14: ...Pump Running LED should turn on 3 Turn the HOA switch to the Off position 4 The pump should stop immediately and the Pump Running LED should turn off Automatic Pressure Start 1 Turn the HOA switch to...

Page 15: ...g manual or automatic Pump Stopped The pump has stopped running manual or automatic Pressure Sensor Fault A pressure sensor fault alarm has occurred HOA Switch Fault An HOA Switch fault alarm has occu...

Page 16: ...t regulations which is applicable in all EC countries At the end of the service life of the equipment the company offers to collect and dispose of this equipment in accordance with regulations in forc...

Page 17: ...21 Publication 245 EN November 2013 Printed in USA Replacement Parts For replacement parts contact your local Metron sales office or the Metron factory at United States Telephone 1 336 434 2800 FAX 1...

Reviews: