6.3.1.2 Parameter Sync
Procedure
Step 1 After replacing components, log in to the ECC800-Pro WebUI and choose
Maintenance > Parameter Sync to access the parameter synchronization page.
Step 2 Click Device type and select the component type from the drop-down list.
Step 3 Select the failed device in Source Device, select the reserved device in Target
Device, and click Submit to synchronize the configuration parameters of the
failed device to the reserved device.
----End
6.3.2 Replacing ECC800-Pro Parts
6.3.2.1 Replacing an ECC800-Pro Main Control Module
Prerequisites
NO TICE
● The ECC800-Pro main control module is hot-swappable.
● Before disconnecting cables from the ECC800-Pro main control module, label
the cables based on the corresponding ports.
●
Tools: ESD wrist strap, ESD gloves, Phillips screwdriver, label, marker
●
Materials: A spare undamaged and undeformed ECC800-Pro main control
module of the same model is available.
Procedure
Step 1 Use the Back Up Current Settings function to record the ECC800-Pro
configuration information or manually record the information.
Path: Maintenance > Configuration File > Back Up Current Settings
NO TE
If the main control module is damaged, login may fail and backup cannot be performed.
The following information cannot be backed up: monitoring module IP address parameters,
smart module certificate, NetEco certificate, NetEco re-authentication password, time
configuration parameters, access user management, access permission management, device
access certificate, log, and user configuration information.
Step 2 Label each cable and antenna based on the corresponding ports on the ECC800-
Pro main control module.
Step 3 Remove cables, USB flash drive, USB-to-WiFi module, and antennas from the
ECC800-Pro main control module.
FusionModule2000-S Smart Modular Data Center
User Manual
6 Operation and Maintenance
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
244