NO TICE
● The default address of T/H sensors purchased from Huawei is 1.
● Keep the last RS485_R toggle switch in OFF position.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H Sensor on the home screen, and set the sensors in the aisles
corresponding to the addresses to Enable. Otherwise, the sensors will not work.
----End
3.10.14 Installing a Smoke Detector
Preparations
Material: smoke detector
Procedure
Step 1 Attach the smoke detector to the top of the enclosure frame at the rear of the
PDF or integrated UPS by magnet.
NO TE
In the NMW scenario, attach the smoke detector to the rear top of the first smart cooling
product.
Step 2 Route the smoke detector cable through the reserved cable hole, connect one end
of the cable to the smoke detector, and the other end to the AI/DI_1 port on the
ECC800-Pro.
----End
3.10.15 Routing a Cable to a WLDS900 Water Sensor
If the water sensor is required, perform the following steps to install it.
Context
●
The water sensor is composed of the water detection cable (BOM number:
33010445), water detector (BOM number: 33010352), and conversion cable
(packed with the water detector).
●
The water detector is installed at the bottom of the equipment.
●
The conversion cable connects the water detection cable to the water
detector.
●
A single water detection cable is 5 m long. If a longer cable is required,
connect the male connector of one water detection cable to the female
connector of another cable. One water detector can be connected to a
maximum of nine water detection cables.
FusionModule2000-S Smart Modular Data Center
User Manual
3 Hardware Installation
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.