4.2.9.11 (Optional) Installing an In-Room Access Actuator
Context
●
The BOM number of an access actuator is 52271874.
●
It is recommended that the access actuator be installed 0.5 m away from the
door edge and 2.2 m above the floor at the inner side of a door.
NO TICE
● The communication distance (network cable length) between the access
actuator and the access control device should not exceed 5 m. If the distance
exceeds 5 m, prepare the cable onsite.
● Before installing the access actuator, install a cable trough or drill a cable hole
in the wall, and route the lead into the trough or hole.
Procedure
Step 1 Take out the waterproof box and remove its cover.
Figure 4-153 Removing the cover of a waterproof box
Step 2 Take out the delivered marking-off template, and mark the mounting holes in the
installation position.
Step 3 Drill holes and install expansion anchor bolt sleeves.
1. Drill holes into the wall to a depth of 45-50 mm using a hammer drill.
Partially tighten the expansion bolts and vertically insert them into the holes.
Knock the expansion anchor bolts using a rubber mallet until the expansion
sleeves are fully inserted into the holes.
2. Partially tighten the nuts clockwise until the expansion anchor bolts and
expansion sleeves are secured to the wall.
3. Loosen the nuts counterclockwise and remove the spring washers and flat
washers.
FusionModule800 Smart Small Data Center
User Manual
4 Installation Guide
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
200