UPS Capacity
Component
Specifications
Output branch circuit breaker
630 A/3P
450 kVA
Mains input circuit breaker
1000 A/3P
Bypass input circuit breaker
800 A/3P
Output branch circuit breaker
800 A/3P
500 kVA
Mains input circuit breaker
1000 A/3P
Bypass input circuit breaker
800 A/3P
Output branch circuit breaker
800 A/3P
550 kVA
Mains input circuit breaker
1250 A/3P
Bypass input circuit breaker
1000 A/3P
Output branch circuit breaker
1000 A/3P
600 kVA
Mains input circuit breaker
1250 A/3P
Bypass input circuit breaker
1000 A/3P
Output branch circuit breaker
1000 A/3P
The circuit breakers recommended in the preceding table are for reference only. Customers need to
connect the circuit breakers outside the UPS.
If multiple loads are connected, specifications for branch circuit breakers must not exceed the
recommended specifications.
The circuit breaker selection principle is to protect loads and cables, and the cascading principle is to
realize specific protection.
The currents listed in the following table are measured at a rated voltage of 480 V.
Table 3-5
Recommended power cable cross-sectional area (50 kVA–300 kVA)
Item
50 kVA
100
kVA
150
kVA
200
kVA
250
kVA
300
kVA
Mains
input
connector
Mains input current (A)
70
140
209
279
349
418
Recommended
cross-sectional
area
(kcmil/AWG)
L1
3 x 3
3 x 3/0
3 x 300
2 x (3 x
3/0)
2 x (3 x
4/0)
2 x (3 x
300)
L2
L3
PE
8
4
4
3
2
1
Bypass
input
connector
Bypass input current (A)
70
140
209
279
349
418
Recommended
cross-sectional
area
L1
3 x 3
3 x 3/0
3 x 300
2 x (3 x
3/0)
2 x (3 x
4/0)
2 x (3 x
300)
L2