UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
A Alarm List
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
193
A
Alarm List
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
0001-1
Mains voltage
abnormal
Minor
Cable
connections are
incorrect.
The mains is not
normal.
The power
module is faulty.
1.
Check whether cables to mains
are disconnected, loose, or
incorrectly connected.
2.
If cable connections are
correct, measure the input
voltage with a multimeter.
380 V AC/400 V AC/415 V
AC/420 V AC voltage
system: If the input voltage
exceeds 485 V, the mains
input is not normal; if the
input voltage is less than
471 V, the sampling circuit
of the power module is not
normal. Replace the faulty
module.
480 V AC voltage system:
If the input voltage exceeds
528 V, the mains input is
not normal; if the input
voltage is less than 514 V,
the sampling circuit of the
power module is not
normal. Replace the faulty
module.
0001-2
Cable
connections are
incorrect.
The mains is not
normal.
The mains input
fuse for the
1.
Check whether cables to mains
are disconnected, loose, or
incorrectly connected.
2.
If cable connections are
correct, measure the input
voltage with a multimeter.
380 V AC/400 V AC/415 V