UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
5 Operations
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
178
Viewing active alarms on the LCD
Choose
System Info
>
Alarms
and tap
Active Alarms
to check that the EPO alarm is
cleared.
Viewing active alarms on the WebUI
Choose
Monitoring
>
Active Alarms
to check that the EPO alarm is cleared.
Step 4
Start the inverter.
----End
5.9 Exporting Data
Prerequisites
You have logged in to the WebUI.
Context
The following data can be exported:
Historical alarms
Logs
E-Label
iBOX version
Fault Data
This topic describes how to export historical alarms.
Procedure
Step 1
Choose
Query
>
Historical Alarms
, and set
Severity
,
Generated
, and
Cleared
.
Figure 5-18
Historical alarms
You do not need to query logs. Choose
Query
>
Logs
, click
Export
, and save the file.
Step 2
Click
Query
, and you can see the corresponding historical alarms.
Step 3
Click
Export
and save the displayed webpage.
----End