UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
5 Operations
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
168
Procedure
Step 1
On the
Settings
>
Dry Contact Set
screen, set
MUE05A connection
to
Enable
, and set
BCB
connection [OL]
and
Battery breaker [STA]
to
Enable
.
Figure 5-5
BCB connection setting
----End
5.2 Shutting Down and Powering Off the UPS
Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is not normal, the UPS supplies no power. Before shutting down the UPS, ensure
that all loads have shut down.
Procedure
Step 1
Shut down the inverter.
On the LCD
a.
On the main screen, tap
Common Functions
. Tap
Inv. OFF
.
b.
If no user is logged in, enter a user name and password, and tap
on the
login screen displayed.
c.
In the displayed dialog box, tap
Yes
to shut down the inverter.