Item
Specifications
Harmonic current
● THDi < 9% (30% linear load), THDi < 6% (50% linear load),
THDi < 3% (100% linear load)
● THDi < 11% (30% non-linear load), THDi < 8% (50% non-linear
load), THDi < 5% (100% non-linear load)
Remarks:
1. The preceding specifications are met when the mains input
and bypass input share a power source.
2. The input THDu is less than 2%.
11.5 Bypass Input Electrical Specifications
Table 11-6 Bypass input electrical specifications
Item
Specifications
Power system
Three-phase four-wire + PE/Three-phase three-wire + PE
Rated voltage
380 V AC/400 V AC/415 V AC (line voltage)
Rated frequency
50 Hz/60 Hz
Frequency range
50 Hz/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz
by default)
Input mode
The mains input and bypass input share a power source (by
default) or use different power sources.
11.6 Battery Electrical Specifications
NO TICE
The UPS supports the SmartLi. For details about the parameters, see the
SmartLi
User Manual
.
UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
11 Technical Specifications
Issue 05 (2021-10-13)
Copyright © Huawei Technologies Co., Ltd.
376