5 Operations
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
234
Figure 5-41
EPO alarm displayed on the WebUI
After you press the EPO button, the
EPO
and
No power supplied
alarms are displayed on the LCD.
5.10 Clearing the EPO State
Procedure
Step 1
Clear the EPO state. Ensure that the EPO button connected to the dry contact card is not in the
EPO state.
Step 2
Clear the EPO alarm.
On the LCD
On the LCD, choose
System Info
>
Alarms
and tap
Clear Faults
. If you have not
logged in, a login screen is displayed. Enter a user name and password, and tap
.