UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
8 Technical Specifications
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
204
Item
UPS5000-E-(25 kVA-75 kVA)
Float voltage: 2.23–2.3 V/Cell, default: 2.25 V/Cell
8.7 Output Electrical Specifications
Item
UPS5000-E-75K-BF
Rated capacity
25 kVA–75 kVA: 25 kVA/50 kVA/75 kVA
Output system
Three-phase, four-wire, and PE
Rated output voltage
380 V AC/400 V AC/415 V AC (line voltage)
Output voltage precision
±1%
Frequency
In normal mode, the mains frequency is
synchronized with the bypass input frequency.
In battery mode, the frequency is 50 Hz or 60 Hz
(tolerance ±0.05%).
Total harmonic distortion (THD)
≤ 1% (full linear load)
≤ 4% (full non-linear load)
Output PF
1
Transfer time
0 ms (uninterruptible transfer)
≤ 20 ms (interruptible transfer)
Output voltage unbalance
Voltage unbalance: ±3%, phase unbalance:
120±2°
Overload capability
Inverter overload capability:
100% < load ≤ 110%: after 60 minutes,
transfer to bypass mode if the bypass is
normal or disconnect output if the bypass is
abnormal
110% < load ≤ 125%: after 10 minutes,
transfer to bypass mode if the bypass is
normal or disconnect output if the bypass is
abnormal
125% < load ≤ 150%: after 1 minute, transfer
to bypass mode if the bypass is normal or
disconnect output if the bypass is abnormal
Load > 150% or in case of short circuit, the
inverter can work for 200 ms.