UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
4 User Interface
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
117
Figure 4-28
Basic Parameter Settings
Single/Parallel
Set the UPS running mode. The value can be
Single
(default) or
Parallel
.
Output voltage level
The value for the system output voltage level can be set as 380 V, 400 V (default), or 415
V. After the parameter value is changed, the upper thresholds for the bypass voltage are
restored to the default values. If
Output voltage level
is 380 V or 400 V, the default
upper threshold is 15% and the default lower threshold is 20%. If
Output voltage level
is 415 V, the default upper threshold is 10% and the default lower threshold is 20%. The
parameter is configurable after the inverter shuts down.
Output frequency (Hz)
Set the system output frequency level. The value can be 50 Hz (default) or 60 Hz.
Battery capacity
Battery string capacity. The value range is 5 Ah to 9999 Ah. The default value is 18 Ah.
Different types of batteries cannot be mixed.
The capacity of each battery module is 9 Ah, at least two strings of battery modules need to be
installed (battery capacity: 9 Ah + 9 Ah = 18 Ah). A maximum of four battery cabinets can be
connected (battery capacity: 9 Ah x 36 = 324 Ah). Therefore, the value range of the battery capacity
is 18 Ah to 324 Ah.
Number of cells
Number of battery cells. Each 12 V battery consists of six cells. The default value is 240
which is not configurable.
A cell consists of electrodes and electrolytes, which is the basic unit for the battery. Each cell has a
nominal voltage of 2 V. A battery is a module consisting of single or multiple cells in a shell. Each
battery has a nominal voltage of 2 V or 12 V.
Cell float voltage,
Cell equalized volt
,
Float volt. temp. comp. coef.
, and
EOD voltage threshold
are set for cells.