UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
103
Figure 3-55
Preparing a cable terminal outside the cabinet
Choose an appropriate cabling route based on the actual situation. The figure is for reference only.
Step 4
Connect the cable with a crimped terminal to the corresponding copper bar.
Step 5
Clean foreign matter inside the cabinet.
----End
3.2.6 Routing Cables (400 kVA, 500 kVA, or 600 kVA UPS)
3.2.6.1 Top Cable Routing
Context
Route cables through holes, remove the power cable cover, spare power cable cover and
battery cable cover and drill holes. After you drill holes, paste grommet strip to the hole
edge to protect cables. Reinstall the covers on the cabinet.
This section introduces the dual mains scenario. If single mains is used, you do not need to
remove the copper bars between the mains and bypass input terminals or connect the
bypass input cable.
The figures are for reference only. For more information about the recommended cable
cross-sectional area and quantity, refer to
Cables are connected in the same way for the 400 kVA, 500 kVA, and 600 kVA UPS. This
section describes how to connect cables for the 400 kVA UPS.