Figure 3-45 Cable connections for a dual-bus system
(1) Mains input power
cables
(2) Bypass input power
cables
(3) Battery cables
(4) Output power
cables
----End
3.4.3 Connecting Signal Cables
Context
This topic describes how to connect signal cables as a loop for four UPSs in a
parallel system.
Procedure
Step 1 Connect the parallel ports on the UPSs using parallel cables to form a loop.
●
shows the topology diagram for the N+X parallel system and
shows the cable connections for this system.