UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
8 Technical Specifications
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
166
Item
Specifications
At 0–30°C
100% < load ≤ 110%: after 60 minutes, transfer to
bypass mode if the bypass is normal or disconnect
output if the bypass is abnormal.
110% < load ≤ 125%: after 10 minutes, transfer to
bypass mode if the bypass is normal or disconnect
output if the bypass is abnormal.
125% < load ≤ 150%: after 1 minute, transfer to
bypass mode if the bypass is normal or disconnect
output if the bypass is abnormal.
Load > 150% or in case of shout circuit, the
inverter can work for 200 ms.
At 30–40°C
100% < load ≤ 110%: after 60 minutes, transfer to
bypass mode if the bypass is normal or disconnect
output if the bypass is abnormal.
110% < load ≤ 125%: after 3 minutes, transfer to
bypass mode if the bypass is normal or disconnect
output if the bypass is abnormal.
125% < load ≤ 150%: after 30 second, transfer to
bypass mode if the bypass is normal or disconnect
output if the bypass is abnormal.
Load > 150% or in case of shout circuit, the
inverter can work for 200 ms.
8.9 System Electrical Specifications
Item
Specifications
Power distribution system
TT, TN-C, TN-S, and TN-CS
ECO in a parallel system
Supported