UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
8 Technical Specifications
Issue 01 (2020-04-27)
Copyright © Huawei Technologies Co., Ltd.
164
8.5 Mains Input Electrical Specifications
Item
Specifications
Input system
Three-phase, four-wire, and PE
Rated input voltage
380 V AC/400 V AC/415 V AC (line voltage)
Input voltage range
80–280 V AC (phase voltage)
At 30–40°C: The UPS works at full load when the
voltage is 187–280 V AC and is derated to 40%
load when the voltage is 187–80 V AC.
At 0–30°C: The UPS works at full load when the
voltage is 176–280 V AC and is derated to 40%
load when the voltage is 176–80 V AC.
Rated frequency
50 Hz / 60 Hz
Input frequency range
40–70 Hz
Input power factor
> 0.99 (full load)
> 0.98 (half load)
THDi
≤ 3% (linear load)
≤ 5% (non-linear load)
8.6 Bypass Input Electrical Specifications
Item
Specifications
Rated input voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input voltage range
Upper threshold: +10%, +15% (default), +20%, +25%
(when the voltage system is 380 V AC)
Upper threshold: +10%, +15% (default), +20% (when the
voltage system is 400 V AC)
Upper threshold: +10% (default), +15% (when the voltage
system is 415 V AC)
Lower threshold: –10%, –15%, –20% (default), –30%,
–40%, –50%, –60%
Input system
Three-phase, four-wire, and PE
Rated frequency
50 Hz / 60 Hz
Frequency range
50/60 Hz ±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default)