SUN2000-63KTL-JPH0
User Manual
5 Electrical Connections
Issue 04 (2019-06-30)
Copyright © Huawei Technologies Co., Ltd.
48
Figure 5-10
Installing the DC input power cable
(1) Positive metal contact
(female)
(2) Negative metal contact
(male)
(3) UTXTC0003
(Amphenol)
(4) Positive connector
(5) Negative connector
(6) UTXTWA001
(Amphenol)
If the DC input power cable is reversely connected and DC switches are set to
ON
, do not
turn off the DC switches immediately or unplug positive and negative connectors. The device
may be damaged if you do not follow the instruction. The caused equipment damage is
beyond the warranty scope. Wait until the solar irradiance declines and the PV string current
reduces to below 0.5 A, and then turn off the two DC switches and remove the positive and
negative connectors. Correct the string polarity before reconnecting the string to the
SUN2000.
----End
5.7 Connecting the RS485 Communications Cable
When routing the communications cable, separate it from power cables to prevent
communication from being affected. Connect the shield layer to the PE point.
Connect the RS485 communications cable to either a terminal block (recommended) or
an RJ45 network port.