No.
Parameter
Description
Unit
7
Grid reconnection
voltage lower limit
The standards of certain countries and regions
require that the SUN2000 must not export
power to the power grid again when the grid
voltage is below the value of Grid
reconnection voltage lower limit after the
SUN2000 shuts down due to a fault.
V
8
Grid reconnection
frequency upper limit
The standards of certain countries and regions
require that the SUN2000 must not export
power to the power grid again when the grid
frequency exceeds the value of Grid
reconnection frequency upper limit after the
SUN2000 shuts down due to a fault.
Hz
9
Grid reconnection
frequency lower limit
The standards of certain countries and regions
require that the SUN2000 must not export
power to the power grid again when the grid
frequency is below the value of Grid
reconnection frequency lower limit after the
SUN2000 shuts down due to a fault.
Hz
10
Reactive power
compensation (cosφ-
P) trigger voltage
Specifies the voltage threshold for triggering
reactive power compensation based on the
cosφ-P curve.
%
11
Reactive power
compensation (cosφ-
P) exit voltage
Specifies the voltage threshold for exiting
reactive power compensation based on the
cosφ-P curve.
%
7.2.2.2 Setting Protection Parameters
Procedure
Step 1 Choose Function Menu > Settings > Protection Parameters to access the
settings screen.
SUN2000-(60KTL, 65KTL)-M0
User Manual (Mexico Edition)
7 Man-Machine Interactions
Issue 06 (2020-10-12)