7
Device Maintenance
7.1 Routine Maintenance
●
Ensure that the SmartLogger is free from strong electromagnetic interference.
●
Ensure that the SmartLogger is away from heat sources.
●
Regularly clean the SmartLogger.
●
Regularly check that cables are secured.
7.2 Troubleshooting
No.
Fault
Cause
Suggestions
1
The
SmartLogge
r cannot be
powered on.
1. The DC output power cable for
the power adapter is not
connected the 12V IN port of the
SmartLogger.
2. The power cable is not connected
to the AC power input port of the
power adapter.
3. The AC input power cable is not
connected to the AC socket.
4. The power adapter is faulty.
5. The SmartLogger is faulty.
1. Connect the DC output power
cable for the power adapter to
the 12V IN port of the
SmartLogger.
2. Check that the power cable is
connected to the AC power input
port of the power adapter.
3. Check that the power cable is
connected to the AC socket.
4. Replace the power adapter.
5. Contact the dealer or Huawei
technical support.
SmartLogger3000
User Manual
7 Device Maintenance
Issue 10 (2022-08-20)
Copyright © Huawei Technologies Co., Ltd.
230