4 Electrical Connection
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
45
Figure 4-3
Removing the terminal block
Use a flat-head screwdriver to remove the terminal block.
Step 3
Connect cables to the terminal block and secure the cables.
Figure 4-4
Connecting cables
Step 4
Insert the terminal block into the COM port.
----End
4.4 Connecting a PE Cable to the SmartLogger
Prerequisites
The PE cable and OT terminal are available.
Recommended PE cable: an outdoor copper-core cable with a cross sectional area of 4–6
mm
2
or 12–10 AWG
OT terminal: M6