SmartLogger1000
User Manual
7 WebUI
Issue 12 (2019-01-15)
Copyright © Huawei Technologies Co., Ltd.
212
You can click the
,
,
, or
tab on the tertiary navigation tree to query related information.
The
Performance Data
of the PID-SSC can be exported. When changing the name of the exported
file, retain the extension
.tar.gz
. Otherwise, the file will be unavailable.
7.8.8.2 Setting Running Parameters
Because of permission restriction, log in as
Advanced user
. Choose
Monitoring
>
PID-SSC
>
Running Param.
to enter the target page.
Figure 7-33
Setting running parameters
Parameter
Description
Operation mode
Specifies the current working mode of the PID module.
Set this parameter to
Commissioning
during commissioning
after deployment or fault locating. In this case, the PID-PVBOX
delivers the output voltage based on the value of the
commissioned output voltage.
Set this parameter to
Normal
after ensuring that the PID module
works normally.
Commissioning
output voltage
Specifies the output voltage when the PID module works in
commissioning mode. It is recommended that
Commissioning
output voltage
be set to a value greater than 250 V.
7.8.9 Custom Device
Custom Device
: The SmartLogger can connect to the third-party devices supporting the
Modbus-RTU protocol, such as the box-type transformer and environmental monitoring
instrument (EMI). Since the protocol information points vary depending on vendors, you need
to obtain a protocol information file in
.cfg
format from Huawei and import the file into the
SmartLogger for successfully connecting to a third-party device.
The SmartLogger supports the connection to a maximum of 10 types of custom devices and can connect
to multiple devices of the same type.